DGV10 F4 RESILIENT SEATED GATE VALVE

Devinsan offers durable, leak‑free shut‑off solutions engineered for reliable performance in water supply, wastewater treatment, and fire protection networks. Designed for long service life, these valves combine robust construction with precise flow control to meet the demands of modern infrastructure

Production Standard

Nominal Dimension (DN)

Nominal Pressure (PN)

Operating Temperature

Design

Face to Face

Connection

Coating

Testing

DN 40 – DN 800

PN 6-PN 10-PN 16-PN 25-PN 40

-30° / +200­­°

EN 1171 – EN 1074

EN 558 Series 14 – DIN 3202 F4

EN 1092-2 ISO7005-2 Flanged

Electrostatic Powder Epoxy

EN 12266-1

Operation Versions

The DGV10 F4 Resilient Seated Gate Valve can be operated with a range of compatible accessories to suit different installation and automation requirements:

1. DVA10 Surface Box & Extension Spindle

2. DVA11 Telescopic Extension Spindle

3. DVA12 Electric Actuators

4. DVA13 Pneumatic Actuators

5. DVA14 Gear Box

6. DVA15 HandWheel

These accessories allow the valve to be adapted for manual, geared, pneumatic, or electric operation, ensuring precise control and reliable performance in both industrial and commercial systems.

Application Areas

The DGV10 F4 Resilient Seated Gate Valve is widely used across diverse industrial and commercial sectors, delivering reliable flow control and long‑lasting performance.

1. Water and Wastewater Systems

2. Chemical Industry

3. Food and Beverage Industry

4. Pharmaceutical Industry

5. Oil and Gas Industry

6. HVAC (Heating, Ventilation, Air Conditioning) Systems

In these applications, this F4 type gate valve ensures precise fluid control, maintains excellent sealing integrity, and supports efficient, safe operation even under demanding conditions.

The DGV10 F4 Resilient Seated Gate Valve is a high‑performance isolation valve engineered for precise and dependable flow control in water supply, wastewater treatment, and fire protection systems. Designed to meet the demands of modern infrastructure, this gate valve delivers exceptional sealing performance, operational reliability, and long‑term durability in both industrial and commercial applications.

At the heart of the DGV10 F4 is a resilient elastomer‑coated wedge that travels vertically within the valve body through a precision‑threaded spindle mechanism. This advanced design ensures smooth, low‑torque operation and a tight shut‑off, effectively preventing leakage even under high‑pressure or fluctuating flow conditions. The elastomer sealing surface provides complete flow isolation when closed, enhancing safety and efficiency in critical fluid networks.

Manufactured from corrosion‑resistant materials and built with a robust, ductile iron body, this resilient seated gate valve is designed to withstand harsh operating environments. Its compact F4 face‑to‑face dimensions allow easy integration into pipeline systems, while the straightforward maintenance process reduces downtime and operational costs.

The DGV10 F4 gate valve is ideally suited for municipal water distribution, irrigation systems, HVAC networks, and fire safety installations, where consistent performance and leak‑free operation are essential. Its versatility also makes it a preferred choice for engineers and project managers seeking a reliable, standards‑compliant solution for long‑term infrastructure performance.

In summary, the DGV10 F4 Resilient Seated Gate Valve offers an optimal combination of performance, efficiency, and safety. With its precision‑engineered sealing system, durable construction, and ease of maintenance, it stands as a trusted solution for modern fluid control applications worldwide

1. General Information

The DGV10 F4 Resilient Seated Gate Valve is designed for use in water distribution networks, water treatment plants, and other applications requiring reliable shut-off. Proper installation is essential to ensure safe operation, long service life, and leak-free performance.

2. Safety Precautions

Installation must be performed by qualified personnel only.

Ensure compliance with all local safety regulations and standards.

Wear appropriate personal protective equipment (PPE).

Confirm that the pipeline is depressurized and drained before installation.

3. Pre-Installation Checklist

Inspect the valve for any visible damage during transport or storage.

Check that the valve type, size, and pressure rating match the system requirements.

Verify that the valve is clean and free from debris.

Confirm that the pipeline ends are properly aligned and free from burrs or sharp edges.

Ensure sufficient space is available for operation and maintenance.

4. Installation Procedure

Positioning: Install the valve in the correct flow direction as indicated by the arrow on the valve body. The valve can be installed in horizontal or vertical pipelines, with the spindle oriented vertically upward for optimal performance.

Pipeline Preparation: Ensure the pipeline is clean and free from dirt, sand, or foreign particles. Use proper gaskets suitable for the medium and operating conditions.

Mounting the Valve: Align the valve with the pipeline flanges. Insert bolts and tighten them crosswise in gradual steps to ensure even compression of the gasket. Do not use excessive force that may damage the valve body or flanges.

Operational Check: Open and close the valve fully to confirm smooth operation. Ensure the valve closes tightly without leakage.

5. Post-Installation

Slowly pressurize the system and check for leaks around the connections.

If leakage is detected, depressurize and re-tighten the bolts.

Record the installation details for documentation.

Installation of DGV10 F4 resilient seated gate valve with flanged connection and EPDM wedge

Proper maintenance extends the service life of the valve and ensures reliable performance. Follow the guidelines below:

1. Routine Operation

Operate the valve (open/close) periodically to prevent seizure and buildup of deposits on the sealing surfaces.

Avoid using the valve for throttling, as it is designed for on/off service.

2. Inspection Schedule

Monthly: Check for external leaks around body joints, stem packing, and flange connections.

Quarterly: Operate the valve fully open and fully closed to verify smooth operation.

Annually: Perform a detailed inspection including seals, stem, and coating condition.

3. Lubrication

If applicable, lubricate the stem nut or gearbox according to manufacturer’s recommendations.

Ensure moving parts remain free of dirt and corrosion.

4. Seal and Gasket Replacement

Replace stem seals, O-rings, and gaskets if leakage or wear is observed.

Always depressurize and drain the pipeline before performing any maintenance work.

Only use original spare parts to guarantee compatibility and reliability.

5. Cleaning

Keep the exterior of the valve clean to prevent corrosion.

In aggressive environments, consider applying additional protective coating or insulation.

6. Storage and Spare Parts

Store spare parts in a dry, clean environment, away from direct sunlight.

Maintain a record of all inspections, repairs, and replacements.

We prioritize quality at every stage of production to deliver durable, safe, and efficient products. Our continuous improvement and strict quality controls keep us at the forefront of the industry.

Our certifications prove our commitment to excellence and compliance with international standards, ensuring the safety and reliability of our products worldwide.

We continuously invest in innovation and quality to expand our certifications and meet evolving industry needs.

Frequently Asked Questions about the DGV10

What are the main advantages of this valve?

The DGV10 F4 Resilient Seated Gate Valve offers low‑torque operation, exceptional corrosion resistance, and maximum sealing performance thanks to its EPDM‑coated wedge. Its robust, maintenance‑free design helps reduce operating costs and ensures long‑term reliability in demanding fluid control applications.

Fully compliant with the DIN 3202 F4 standard, this model is engineered to meet European market requirements, providing precise flow isolation and dependable performance across a wide range of water, wastewater, and fire protection systems.

This valve delivers outstanding performance in both sealing and durability, making it a dependable choice for demanding applications. Its high‑quality epoxy coating protects against corrosion and environmental factors, ensuring reliable operation over time. Designed for easy installation, it can be mounted in both vertical and horizontal positions, offering flexibility during system design. With a wide range of diameter options, it meets the needs of various infrastructure projects, from municipal water networks to industrial facilities.

The valve features a robust flanged connection for secure pipeline integration. Before installation, the pipeline interior should be thoroughly cleaned and flange faces precisely aligned to ensure proper sealing. Once the sealing gaskets are positioned, bolts must be tightened evenly with consistent torque to prevent leakage. Designed for versatility, it can be installed in either vertical or horizontal orientations, making it suitable for a wide range of system layouts.

This model is manufactured in accordance with the DIN 3202 F4 face‑to‑face dimension standard and is designed to meet international quality requirements. Its EPDM‑coated wedge ensures high sealing performance, while the body material and protective coating meet European market expectations for corrosion resistance and durability. As a result, it can be confidently used in both municipal infrastructure projects and industrial facilities.

Yes. The DGV10 F4 is designed for flexible installation and can be mounted in either vertical or horizontal pipeline configurations without affecting performance. Its flanged connection ensures secure integration, while proper alignment and even bolt tightening during installation guarantee optimal sealing. This versatility makes it suitable for a wide range of system layouts in municipal, industrial, and fire protection networks.

Contact Devinsan

Reach out to our team for inquiries, quotes, and technical assistance